EWS1 ratings explained: A1, A2, A3, B1 and B2

Every EWS1 form ends with one of five ratings. Here is what each one means, how lenders tend to treat it and what to do next.

Updated 21 November 2026

In short

  • Every EWS1 form ends with one of five ratings: A1, A2, A3, B1 or B2.
  • Option A ratings apply where the external wall materials are unlikely to support combustion. Option B ratings apply where combustible materials are present in the wall.
  • A1, A2 and B1 mean no remedial works are needed, and many lenders will lend on them.
  • A3 means there may be remedial costs for attachments such as balconies. B2 means remedial works are required.

Option A and Option B

The signatory of an EWS1 form first chooses one of two routes. Option A is for buildings where the materials in the external wall are of limited combustibility or better, so they are unlikely to support combustion. Option B is for buildings where combustible materials are present in the external wall, and the question becomes whether the resulting fire risk is acceptable. Option B calls for a higher level of fire risk expertise.

A1 rating

The external wall materials are unlikely to support combustion, and there are no attachments, such as balconies, whose construction includes significant quantities of combustible material. No remedial works are needed. This is the cleanest outcome a building can get.

A2 rating

The wall materials are unlikely to support combustion, but attachments such as balconies do include combustible material. An appropriate risk assessment of those attachments confirms that no remedial works are required. No action is needed.

A3 rating

Neither A1 nor A2 applies. The walls themselves are fine, but there may be costs of remedial works to attachments, usually balconies. Lenders often treat A3 cautiously, and some will not lend until the works are done or costed.

B1 rating

Combustible materials are present in the external wall, but the fire risk appraisal finds the risk sufficiently low that no remedial works are required. Many lenders accept B1. It shows the value of a proper PAS 9980 appraisal: combustible does not automatically mean unsafe.

B2 rating

Combustible materials are present and the fire risk is high enough that remedial works are required. Interim measures may also be needed while works are planned. Most lenders will not lend on a B2 building until remediation is complete or funded.

EWS1 ratings at a glance

RatingCombustible materials in the wall?Works needed?Typical lender view
A1NoNoUsually acceptable
A2No, but some in attachmentsNoUsually acceptable
A3No, but in attachmentsPossibly, to attachmentsOften cautious
B1YesNoUsually acceptable
B2YesYesUsually not until works are done

Each lender sets its own policy, so always check with the lender involved.

What to do with an A3 or B2 rating

  • Read the FRAEW, not just the form. The FRAEW report explains exactly what needs doing and why.
  • Check funding. The Cladding Safety Scheme covers many buildings of 11 metres and above outside London and 11 to 18 metres in London. The Developer Remediation Contract may also apply.
  • Get prices for the works. A clear, costed plan often helps lenders and buyers.
  • Reassess after works. Once remediation is complete, a new appraisal and EWS1 form can record the improved rating.
Need a new EWS1 rating for your block?

PAS 9980:2026 appraisal and signed form, fixed price for blocks under 18 metres.

Start a free check

EWS1 rating questions

Which EWS1 ratings do lenders accept?

Many lenders accept A1, A2 and B1, because no remedial works are needed. A3 and B2 are often treated as unacceptable until works are completed or funded. Each lender sets its own policy.

Is B1 worse than A1?

Not for lending purposes. Both mean no remedial works are needed. B1 means combustible materials are present but the appraisal has found the risk low enough to be acceptable.

Can an EWS1 rating be improved?

Yes. After remediation works, a new appraisal and EWS1 form can record the improved rating.